  speed and accuracy for test optimization C 8-slot mainframe accepts up to 8 dc power modules C 1200 w total dc power output, up to 150 w per module C reconigure fast with easily swappable modules C fast, low-noise outputs C list mode and advance triggering system C optional isolation and polarity reversal relays C built-in measurements and advanced programmable features C protection features to ensure dut safety data sheet keysight technologies 66000A 1200 w dc modular power system,gpib
02 | keysight | 66000A 1200 w dc modular power system, gpib - data sheet 66000 modular power system keysight technologies, inc. 66000 modular power sys tem simplifies test-system assembly, cabling, programming, debugging and operation. it is ideal for ate and production test environments, where it can supply bias power and stimulus to subas semblies and final products. the modular power system saves rack space, the 7-inch-high (4-eia units) mainframe can accommodate up to eight dc power modules. key features ? gpib-programmable voltage and current ? programmable over-voltage and over-current protection ? self-test initiated at power-up or from gpib command ? electronic calibration over gpib or from keyboard ? over-temperature protection ? discrete fault indicator/remote inhibit (dfi/ri) ? five nonvolatile store-recall states per output ? user-definable power-on state multiple mainframes at one gpib address the keysight serial link feature will allow you to control up to 16 outputs at one gpib address by connecting an auxiliary mainframe. the serial link cable comes standard with the 66000 mps mainframe. for applications with a broader range of power requirements, one 66000 mainframe can be connected with up to eight of the 6640, 6650, 6670, 6680, 6690 or 6030 series of system power supplies. this solution provides power ranges from 150 watts to 5000 watts at one primary gpib address. output connections system assembly is simplified thanks to a quick-dis connect connector assembly on each module. once your wires are connected to the load, the connector design permits the modules to be removed from the front of the mainframe without disconnecting cabling or removing the mainframe from the rack. one connector assembly is shipped with each module. output sequencing increase test throughput by using the output sequencing feature of the 66000 mps. this powerful feature allows you to download up to 20 voltage, current, and dwell-time parameter sets per output. this sequence can be paced by the programmed dwell times. as an alternative, triggers can be used to step through the output list. the output sequences can be executed without controller intervention, thereby increasing overall test system throughput.
03 | keysight | 66000A 1200 w dc modular power system, gpib - data sheet speciications supplemental characteristics (non-warranted characteristics determined by design and useful in applying the product) 66101a 66102a 66103a 66104a 66105a 66106a average programming resolution voltage current over voltage protection(ovp) 2.4 mv 4.6 ma 50 mv 5.9 mv 2.3 ma 120 mv 10.4 mv 1.4 ma 200 mv 18.0 mv 0.75 ma 375 mv 36.0 mv 0.39 ma 750 mv 60.0 mv 0.23 ma 1.25 mv ovp accuracy 250 mv 500 mv 800 mv 1 v 1.5 v 2.5 v specifications(at 0 to 55 c unless otherwise specified) 66101a 66102a 66103a 66104a 66105a 66106a output ratings at 40c output voltage output current maximum power 0 to 8 v 0 to 16 a 128 w 0 to 20 v 0 to 7.5 a 150 w 0 to 35 v 0 to 4.5 a 150 w 0 to 60 v 0 to 2.5 a 150 w 0 to 120 v 0 to 1.25 a 150 w 0 to 200 v 0 to 0.75 a 150 w programming accuracy (at 25 c 5 c) voltage 0.03% + current 0.03% + 3 mv 6 ma 8 mv 3 ma 13 mv 12 ma 27 mv 1.2 ma 54 mv 0.6 ma 90 mv 0.4 ma readback accuracy (via gpib or keyboard dis- play at 25 c 5 c) voltage 0.02% + current 0.02% + 2 mv 6 ma 5 mv 3 ma 8 mv 2 ma 16 mv 1 ma 32 mv 0.6 ma 54 mv 0.3 ma ripple and noise from 20 hz to 20 mhz constant voltage rms peak-to-peak constant current rms 2 mv 5 mv 8 ma 3 mv 7 mv 4 ma 5 mv 10 mv 2 ma 9 mv 15 mv 1 ma 18 mv 25 mv 1 ma 30 mv 50 mv 1 ma line regulation voltage current 0.5 mv 0.75 ma 0.5 mv 0.5 ma 1 mv 0.2 ma 2 mv 0.1 ma 3 mv 50 a 5 mv 30 a load regulation voltage current 1 mv 0.5 ma 1 mv 0.2 ma 1 mv 0.2 ma 2 mv 0.1 ma 4 mv 50 a 7 mv 30 a transient response time less than 1 ms for the output voltage to recover within 100 mv of its previous level following any step change in load current up to 10 percent of the power module rated output current
04 | keysight | 66000A 1200 w dc modular power system, gpib - data sheet speciications, continued supplemental characteristics (non-warranted characteristics determined by design and useful in applying the product) 66101-j03 special order option 66101-j05 special order option 66101-j05 special order option 66103-j01 special order option 66103a-j02 special order option average programming resolution voltage current ovp 2 mv 6 ma 45 mv 3,6 mv 4.6 ma 75 mv 4.5 mv 31 ma 90 mv 11 mv 1.4 ma 200 mv 12 mv 1.2 ma 230 mv ovp accuracy 250 mv 375 mv 375 mv 850 mv 920 mv specifications(at 0 to 55 c unless otherwise specified) 66101-j03 special order option 66101-j05 special order option 66101-j05 special order option 66103-j01 special order option 66103a-j02 special order option output ratings at 40c output voltage output current maximum power 5.7 v 20 a 114 w 12 v 12 a 144 w 15 v 10 a 150 w 37 v 4.5 a 167 w 40 v 3.6 a 144 w programming accuracy (at 25 c 5 c) voltage 0.03% + current 0.03% + 2.5 mv 8 ma 5 mv 6 ma 8 mv 4 ma 13 mv 2 ma 15 mv 2 ma readback accuracy (via gpib or keyboard display at 25 c 5 c) voltage 0.02% + current 0.02% + 2 mv 8 ma 3 mv 6 ma 5 mv 4 ma 8 mv 2 ma 9.2 mv 2 ma ripple and noise from 20 hz to 20 mhz voltage rms peak-to-peak current rms 2 mv 5 mv 10 ma 3 mv 7 mv 8 ma 3 mv 7 mv 6 ma 5.3 mv 10.6 mv 2 ma 6 mv 11.5 mv 2 ma line regulation voltage current 0.5 mv 0.5 ma 0.5 mv 0.75 ma 0.5 mv 0.5 ma 1 mv 0.3 ma 1 mv 0.3 ma load regulation voltage current 1 mv 1 ma 1 mv 0.5 ma 1 mv 0.3 ma 1 mv 0.2 ma 1 mv 0.2 ma transient response time less than 1 ms for the output voltage to recover within 100 mv of its previous level following any step change in load current up to 10 percent of the power module rated output current
05 | keysight | 66000A 1200 w dc modular power system, gpib - data sheet speciications, continued supplemental characteristics (non-warranted characteristics determined by design and useful in applying the product) 66103a-j09 special order option 66103a-j12 special order option 66104a-j09 special order option 66105a-j01 special order option average programming resolution voltage current ovp 10.4 mv 2 ma 200 mv 8 mv 2 ma 150 mv 16.5 mv 0.9 ma 350 mv 2 mv 1.2 ma 230 mv output accuracy 800 mv 600 mv 950 mv 920 mv specifications(at 0 to 55 c unless otherwise specified) 66103a-j09 special order option 66103a-j12 special order option 66104a-j09 special order option 66105a-j01 special order option output ratings at 40c output voltage output current maximum power 28.5 v5.5 a 157 w 24 v6 a 144 w 55 v3 a 165 w 35 v1.25 a 44 w programming accuracy at 25 c 5 c voltage 0.03% + current 0.03% + 13 mv 3 ma 13 mv 3 ma 25 mv 1.5 ma 15 mv 11 ma readback accuracy (via gpib or keyboard display at 25 c 5 c) voltage 0.02% + current 0.02% + 8 mv 3 ma 8 mv 3 ma 15 mv 1.2 ma 9 mv 0.6 ma ripple and noise from 20 hz to 20 mhz constant voltage rms peak-to-peak constant current rms 5 mv 10 mv 4 ma 5 mv 10 mv 4 ma 9 mv 15 mv 1.2 ma 6 mv 11.5 mv 1 ma line regulation voltage current 1 mv 0.3 ma 1 mv 0.3 ma 2 mv 0.1 ma 1 mv 50 a load regulation voltage current 1 mv 0.2 ma 1 mv 0.2 ma 2 mv 0.1 ma 1 mv 50 a transient response time less than 1 ms for the output voltage to recover within 100 mv of its previous level following any step change in load current up to 10 percent of the power module rated output current
06 | keysight | 66000A 1200 w dc modular power system, gpib - data sheet keysight models: 66000A supplemental characteristics for all model numbers dc floating voltage: output terminals can be floated up to 240 vdc from chassis ground remote sensing: up to half the rated output voltage can be dropped across each load lead. add 2 mv to the voltage load regulation specification for each 1 v change in the negative output lead caused by a load current change. command processing time: the average time for the output voltage to change after getting an gpib command is 20 ms. output programming response time (with full resistive load): the rise and fall time (10% to 90% and 90% to 10%) of the output voltage is less than 20 ms. the output voltage change settles within 0.1% of the final value in less than 120 ms. down programming: an active down programmer sinks approximately 10% of the rated output current calibration interval: one year ac input of system mainframe: voltage 100 vac 120 vac 200 vac 220 vac 230 vac 240 vac max. current 29 a 25 a 16 a 16 a 15 a 15 a input power of system mainframe: 3200 va (max.), 1800 w (max.), 1600 w (typ.) gpib interface capabilities: sh1, ah1, te6, le4, sr1, rl1, pp0, dc1, dt1, e1, and c0, and a command set compatible with ieee-488.2 and scpi software driver: vxiplug&play regulatory compliance: listed to ul 1244; certified to csa 22.2 no. 231; conforms to iec 61010-1 size: 66000A: 425.7 mm w x 192 mm h x 677.93 mm d (16.76 in x 7.28 in x 26.69 in), including feet and rear connectors weight: net, 66000A, 15 kg (33 lb); 66001a, 1.05 kg (2.3 lb); 66101-66106a, 2.8 kg (6 lb). shipping, 66000A, 19 kg (42 lb); 66001a, 1.34 kg (2.95 lb); 66101?66106a, 4.1 kg (9 lb) warranty: one year top front 677.9 mm 26.69" 104.9 mm 4.13" 425.7 mm 16.76" 177.3 mm 6.98" 190 mm 7.5"
07 | keysight | 66000A 1200 w dc modular power system, gpib - data sheet ordering information 66000A mps mainframe the 66000A comes with full documentation on cd-rom. the cd-rom includes user?s guide, installation guide, programming guide, service manu al, quick start guide, and application notes. opt 0l1 printed programming and installation guides. opt 0b3 printed service manual opt 831 power cord, no plug, americas opt 833 power cord, no plug, europe opt 834 power cord, no plug, usa opt 841 power cord, americas, japan, nema 6-20p, 20 a, 250 v plug opt 845 power cord, scandinavia, iec 309, 16 a, 220 v plug opt 846 power cord, north america, nema l5-30p, 30 a, 120 v plug opt 847 power cord, europe, cee 7/7, 16 a, 220 v plug opt 848 power cord, s. africa, india, bs 546, 15 a, 240 v module options each module comes with full documentation on cd-rom opt 760 adds isolation/polarity relays opt j17 external monitor opt 0l1 printed installation sheet and user?s guide opt 0b3 printed service manual accessories 1cm023a* rack mount flange kit 177.0 mm h (4u) ? two flange brackets 1cp013a* rack mount flange and handle kit 177.0 mm h (4u) ? two brackets and front handles e3663ac support rails for keysight rack cabinets 66001a mps keyboard includes 2 m (6 ft) cables 66002a rack kit for 66001a keyboard p/n 5060-3351 field-installable relay kit p/n 5060-3386 standard connector assembly p/n 5060-3387 standard connector assembly with installed relays (option 760) application notes 66000 modular power system product note, 5988-2800en 10 practical tips you need to know about your power products , 5965-8239e 10 hints for using your power supply to decrease test time , 5968-6359e keysight dc power supplies for base station testing, 5988-2386en *support rails required
08 | keysight | 66000A 1200 w dc modular power system, gpib - data sheet mykeysight www.keysight.com/find/mykeysighta personalized view into the information most relevant to you. keysight assurance plans www.keysight.com/find/assuranceplansup to five years of protection and no budgetary surprises to ensure your instruments are operating to specification so you can rely on accurate measurements. www.keysight.com/quality keysight technologies, inc.dekra certified iso 9001:2008 quality management system keysight channel partners www.keysight.com/find/channelpartners get the best of both worlds: keysights measurement expertise and product breadth, combined with channel partner convenience. this information is subject to change without notic e. ? keysight technologies, 2012 - 2014published in usa, august 2, 2014 5990-9310en www.keysight.com for more information on keysight technologies products, applications or services, please contact your local keysight office. the complete list is available at: www.keysight.com/find/contactus americas canada (877) 894 4414 brazil 55 11 3351 7010 mexico 001 800 254 2440 united states (800) 829 4444 asia paciic australia 1 800 629 485 china 800 810 0189 hong kong 800 938 693 india 1 800 112 929 japan 0120 (421) 345 korea 080 769 0800 malaysia 1 800 888 848 singapore 1 800 375 8100 taiwan 0800 047 866 other ap countries (65) 6375 8100 europe & middle east austria 0800 001122 belgium 0800 58580 finland 0800 523252 france 0805 980333 germany 0800 6270999 ireland 1800 832700 israel 1 809 343051 italy 800 599100 luxembourg +32 800 58580 netherlands 0800 0233200 russia 8800 5009286 spain 0800 000154 sweden 0200 882255 switzerland 0800 805353 opt. 1 (de)opt. 2 (fr) opt. 3 (it) united kingdom 0800 0260637 for other unlisted countries:www.keysight.com/find/contactus (bp-07-10-14) www.keysight.com/find/66000


▲Up To Search▲   

 
Price & Availability of 66000A

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X